WEBVTT
Kind: captions
Language: en

00:00:00.000 --> 00:00:03.401
What do you do when you need to control an
electrical device?

00:00:03.401 --> 00:00:05.819
Most of the time we use simple switches.

00:00:05.819 --> 00:00:09.632
Any device, be it a light bulb, desk fan, or toaster oven

00:00:09.632 --> 00:00:13.607
needs to be part of a complete breakfast— 
sorry, circuit in order for it to work,

00:00:13.607 --> 00:00:17.061
so if we put a break somewhere in the circuit…

00:00:17.061 --> 00:00:20.842
then it’s no longer complete and power cannot flow through it.

00:00:20.842 --> 00:00:23.049
And that’s all that most switches do:

00:00:23.049 --> 00:00:28.204
a light switch like this is really just two
weird little bits of wire that come together in the middle,

00:00:28.204 --> 00:00:31.602
and when the plastic toggle is moved to the “off” position,

00:00:31.602 --> 00:00:35.341
they’re pulled apart so power cannot flow through the switch anymore.

00:00:35.654 --> 00:00:39.176
Ideally that happens with a snap-action to minimize arcing,

00:00:39.176 --> 00:00:41.281
and that’s why most switches make a clicking noise,

00:00:41.281 --> 00:00:43.584
but that’s a topic for another video that I’ve already made.

00:00:43.584 --> 00:00:46.977
But what if you want to control something… big?

00:00:46.977 --> 00:00:54.092
A light switch can only break 15, maybe 20 amps of current,
and there’s a lot of stuff that needs more than that.

00:00:54.092 --> 00:01:00.481
Plus, sometimes you have to control something
that runs at a higher voltage, or possibly even uses more phases.

00:01:00.481 --> 00:01:05.628
And what if you want to automate whatever
it is you’re powering with some kind of control system?

00:01:05.628 --> 00:01:08.834
Looks like you’re gonna need a contactor.

00:01:08.834 --> 00:01:12.690
Contactors are the unsung heroes of industrial equipment control.

00:01:12.690 --> 00:01:15.133
They’ve come up a few times on this channel,

00:01:15.133 --> 00:01:21.441
but I’ve never really explained what they are
and why they’re so useful in so many applications.

00:01:21.441 --> 00:01:23.012
Time to fix that!

00:01:23.012 --> 00:01:26.975
Contactors aren’t something you typically find inside the home...

00:01:26.975 --> 00:01:31.300
except for that one just outside — don't worry, we’ll get there.

00:01:31.300 --> 00:01:33.924
A contactor does what it sounds like it does:

00:01:33.924 --> 00:01:36.942
it decides whether there’s contactor not.

00:01:37.725 --> 00:01:38.765
I’m sorry.

00:01:38.765 --> 00:01:43.778
This is a typical two-pole contactor for controlling single-phase loads.

00:01:43.778 --> 00:01:46.292
Notice that there are six electrical connections:

00:01:46.292 --> 00:01:52.239
we have two up top, two down below,
and another smaller pair on the sides of it.

00:01:52.239 --> 00:01:55.084
If I pry this cover off the face of the contactor,

00:01:55.084 --> 00:02:02.036
at first glance what we find appears to be two large copper links
straight from the top connections to the bottom connections,

00:02:02.036 --> 00:02:08.022
but looking from an angle reveals that the center section of
copper is actually floating above the rest.

00:02:08.022 --> 00:02:11.358
Right now, there’s a gap between the top and bottom terminals,

00:02:11.358 --> 00:02:15.781
so this contactor is open and power cannot flow through it.

00:02:15.781 --> 00:02:18.744
That floating middle section can move, though.

00:02:18.744 --> 00:02:25.290
If I push down on one of these little rectangles,
the center links come into contact with the top and bottom links.

00:02:25.551 --> 00:02:29.101
When in this position, power can flow through the contactor.

00:02:29.336 --> 00:02:33.336
Normally, though, it’s not a finger that pushes the contacts together -

00:02:33.336 --> 00:02:36.800
that role is usually handled by an electromagnet.

00:02:36.800 --> 00:02:39.629
And that’s what the terminals on the sides are for.

00:02:39.629 --> 00:02:42.116
Send the appropriate voltage to those terminals,

00:02:42.116 --> 00:02:48.933
and the electromagnet inside pulls down on the center section 
by way of these arches, which bridges the gap like so.

00:02:48.933 --> 00:02:49.608
[CLACK]

00:02:49.608 --> 00:02:53.641
A contactor in this state is often said to be “pulled in,”

00:02:53.641 --> 00:03:01.409
and when the cover is installed the recess created by the moving
contacts provides a visual indicator of the contactor’s current state.

00:03:01.409 --> 00:03:06.670
When power is removed from the electromagnet, of course,
we need the contacts to open back up.

00:03:06.670 --> 00:03:07.170
[THUNK]

00:03:07.170 --> 00:03:10.651
That’s done with not one, but three springs.

00:03:10.651 --> 00:03:18.519
The first is sandwiched between the two cores of the electromagnet
and keeps them physically separated unless the magnet has power.

00:03:18.519 --> 00:03:24.583
That spring is pretty weak, though, so to ensure the separation
of the electrical contacts happens very quickly,

00:03:24.583 --> 00:03:31.370
these additional springs between the arches and the center links become compressed when the contactor is pulled in.

00:03:31.370 --> 00:03:37.745
Once released, they provide an inertial kick
by quickly flinging the arches away at high speed,

00:03:37.745 --> 00:03:41.097
and once they’re extended enough to catch the copper links,

00:03:41.097 --> 00:03:45.810
well they get yanked away and off the contacts just as quickly.

00:03:45.810 --> 00:03:47.488
Now, some of you might be thinking,

00:03:47.488 --> 00:03:52.625
“Wait a minute. So this thing is just an overgrown relay?”
and to you’d I say:

00:03:52.625 --> 00:03:53.943
yeah, pretty much.

00:03:53.943 --> 00:03:55.939
But there are some differences.

00:03:55.939 --> 00:04:01.720
For a start, most relays offer both normally open and normally closed contacts,

00:04:01.720 --> 00:04:09.112
meaning they might actually disconnect something from power when energized,
or even switch power from one path to another.

00:04:09.112 --> 00:04:12.866
Often incorporating multiple sets of each contact type,

00:04:12.866 --> 00:04:18.292
relays can perform fairly complex switching tasks when combined with other circuitry.

00:04:18.292 --> 00:04:22.253
But a contactor is generally just a big power switch.

00:04:22.253 --> 00:04:28.397
And that’s the other difference: 
relays usually aren’t designed to carry much current or handle high voltages,

00:04:28.397 --> 00:04:33.598
but contactors can and do - that’s why it’s so bulky.

00:04:33.598 --> 00:04:38.050
The large gap maintained between the contact points when the contactor is open

00:04:38.050 --> 00:04:43.891
allows it to handle a maximum of 600 volts AC -
much more than a typical relay.

00:04:43.891 --> 00:04:49.800
On top of that,
the thick copper links inside allow this contactor to carry up to 50 amps continuously

00:04:49.800 --> 00:04:52.854
(or 40 amps if it’s not a resistive load).

00:04:52.854 --> 00:04:59.872
And on top of that, its contact points are designed to withstand arcing caused by much higher temporary current spikes,

00:04:59.872 --> 00:05:04.948
like the kind you encounter when switching on
large inductive loads such as motors.

00:05:04.948 --> 00:05:10.515
That’s what the LRA figure is for - that stands for locked rotor amps.

00:05:10.515 --> 00:05:15.059
Induction motors, by far the most common
motor type that this fella will control,

00:05:15.059 --> 00:05:20.889
pull very large amounts of current if the rotor cannot move - or is locked.

00:05:20.889 --> 00:05:22.853
(the rotor is the spinny bit)

00:05:22.853 --> 00:05:28.319
And whenever a motor is started from a stop,
for a brief moment it will pull locked rotor amps -

00:05:28.319 --> 00:05:32.568
which is often several times what it pulls when at operating speed.

00:05:32.568 --> 00:05:38.471
As an example, the compressor in this air conditioner normally draws 12.8 amps at its rated load

00:05:38.471 --> 00:05:40.604
(that’s rated load amps)

00:05:40.604 --> 00:05:44.495
but its locked rotor amp draw is 67.8.

00:05:44.495 --> 00:05:51.169
That really high initial current draw is the reason your lights dim 
for just a moment when your air conditioner switches on.

00:05:51.169 --> 00:05:56.876
Since this can handle a motor that might draw
a whopping 240 amps at startup,

00:05:56.876 --> 00:06:00.214
it sure seems like a decent fit for controlling an air conditioner.

00:06:00.214 --> 00:06:05.134
And wouldn’t ya know it, if we take a peek
inside the electrical cabinet of this air conditioner

00:06:05.134 --> 00:06:07.034
what should we find but…

00:06:07.034 --> 00:06:08.838
a contactor!

00:06:08.838 --> 00:06:11.149
And some other stuff, but don’t worry about all that.

00:06:11.149 --> 00:06:15.876
This contactor is some kinda budget model
that only breaks one leg of the circuit.

00:06:15.876 --> 00:06:17.921
It’s built just like the one we’ve been looking at,

00:06:17.921 --> 00:06:23.019
but the right half of it has turned into a simple link
permanently connecting the top and bottom.

00:06:23.019 --> 00:06:25.825
I can only imagine this is very slightly cheaper.

00:06:25.825 --> 00:06:27.545
Now, here’s the important bit:

00:06:27.545 --> 00:06:31.885
the contactor, or more specifically the gap between its contacts,

00:06:31.885 --> 00:06:37.107
is literally the only thing keeping this air conditioner from running right now.

00:06:37.107 --> 00:06:40.342
Unless you bother to shut off the breaker to it in the winter time,

00:06:40.342 --> 00:06:46.650
the wires on the input side of the contactor
are live at 240V all the time.

00:06:46.650 --> 00:06:50.907
And, since this has this weird bargain-basement single-pole contactor,

00:06:50.907 --> 00:06:56.065
that means every electrical connection in this device
always has 120V potential on it.

00:06:56.065 --> 00:06:57.387
Neat!

00:06:57.387 --> 00:07:03.382
Anyway, if I take a high-tech insulated poking device
and press in on the contactor’s pressy bit

00:07:03.382 --> 00:07:06.750
[BRRGSHSSWMMMMAHHHHHHHH]

00:07:06.750 --> 00:07:08.279
it starts right up.

00:07:08.879 --> 00:07:10.347
Weird, right?

00:07:10.347 --> 00:07:15.941
That contactor really is the only control mechanism in this air conditioner.

00:07:15.941 --> 00:07:19.358
Yeah, this is about as basic an air conditioner as you can get,

00:07:19.358 --> 00:07:23.249
so mediocre it can’t be legally installed in the Southwest!

00:07:23.249 --> 00:07:26.548
But there’s plenty of these machines out there.

00:07:26.548 --> 00:07:33.327
Really, it’s just two motors: a big one in the compressor,
and a smaller one for the condenser fan.

00:07:33.327 --> 00:07:41.313
They both run directly from AC power, and the unit can only ever be on or off, so a simple contactor is all we need.

00:07:41.313 --> 00:07:46.249
[CLACK and then the air conditioner starting]

00:07:46.249 --> 00:07:51.779
But of course, something needs to turn that contactor on
in order to turn the air conditioner on.

00:07:51.779 --> 00:07:53.612
What would that be?

00:07:53.612 --> 00:08:00.865
Well, did you catch that the contactor we've been looking at
has a coil meant to run at 24V AC?

00:08:00.865 --> 00:08:06.200
That might seem like a weird choice,
but that is in fact a very common coil voltage.

00:08:06.200 --> 00:08:11.752
See, although the air conditioner is effectively a standalone device
with its own power supply,

00:08:11.752 --> 00:08:15.955
it needs to cooperate with the rest of the HVAC system it’s a part of.

00:08:15.955 --> 00:08:18.468
In this case, that’s a gas-fired furnace,

00:08:18.468 --> 00:08:24.943
and the control board that operates the furnace
just so happens to run on 24V AC.

00:08:24.943 --> 00:08:29.335
That is in fact the de-facto control voltage in the HVAC world.

00:08:29.335 --> 00:08:35.400
So, then, the furnace supplies power to the contactor
when it wants the air conditioner to run, right?

00:08:35.400 --> 00:08:37.996
Well, only sort of.

00:08:37.996 --> 00:08:42.553
One of the main reasons HVAC systems operate at this low control voltage

00:08:42.553 --> 00:08:48.891
is that we can safely send it through inexpensive thermostat
wire that snakes around wherever it needs to go.

00:08:48.891 --> 00:08:57.079
With a basic four-wire system, the furnace sends its 24V out to a thermostat which can then return it on one of the other three wires:

00:08:57.079 --> 00:08:59.247
one to signal a heating request,

00:08:59.247 --> 00:09:01.032
another for the blower fan,

00:09:01.032 --> 00:09:02.929
and the third for cooling.

00:09:02.929 --> 00:09:06.678
The furnace will respond accordingly to whatever signal it gets back.

00:09:06.678 --> 00:09:13.451
But when the thermostat sends a cooling call,
although it does send 24V back to the furnace on the yellow wire,

00:09:13.451 --> 00:09:17.529
from there it goes right to the contactor outside.

00:09:17.529 --> 00:09:24.441
Take a look, I’ve shut the power off to the air conditioner 
because what I’m about to do is very not good for it.

00:09:24.441 --> 00:09:29.269
If I take the leads of a multimeter set to current
(so basically a jumper wire)

00:09:29.269 --> 00:09:31.253
and do this…

00:09:31.253 --> 00:09:33.358
here’s what’s happening outside.

00:09:33.358 --> 00:09:37.320
[rapid and loud clicking and clacking]

00:09:37.320 --> 00:09:43.082
What I’m doing here is taking the 24V from the red wire
and sending it back on the yellow wire.

00:09:43.082 --> 00:09:45.714
Once it makes it back to the furnace’s control board,

00:09:45.714 --> 00:09:48.442
it becomes spliced with a second wire.

00:09:48.442 --> 00:09:56.699
This one is part of an entirely different run of thermostat wire that follows the refrigerant lineset of the air conditioner all the way outside.

00:09:56.699 --> 00:10:00.159
Once there, it’s wired to the contactor’s coil.

00:10:00.159 --> 00:10:05.433
All a thermostat does when it calls for cooling
is connect these two wires together

00:10:05.433 --> 00:10:12.139
which sends power to this contactor which in turn
sends power to the compressor and condenser fan motor.

00:10:12.139 --> 00:10:19.100
So it is in fact the thermostat which is in
direct control of whether the air conditioner runs or not.

00:10:19.100 --> 00:10:24.964
Of course, the furnace is supplying the 24V AC,
so without it the contactor wouldn’t do anything.

00:10:24.964 --> 00:10:30.785
And this more modern furnace does pay attention
to whether there’s power coming back on the Y terminal

00:10:30.785 --> 00:10:36.529
so it can run the blower motor at a different speed
between fan-only and cooling calls.

00:10:36.529 --> 00:10:41.638
But a lot of older systems had no idea whether
the air conditioner was running or not.

00:10:41.638 --> 00:10:47.930
Thermostats generally send power on both the Y terminal
and the G terminal when calling for cooling,

00:10:47.930 --> 00:10:50.889
and power on G will turn on the blower fan.

00:10:50.889 --> 00:10:55.106
So in older setups, as far as the furnace or air handler knew

00:10:55.106 --> 00:10:57.520
it was just supposed to be running the fan.

00:10:57.520 --> 00:10:59.589
It had no idea why.

00:10:59.589 --> 00:11:03.240
So by now, I’m sure you get the point of having that contactor.

00:11:03.527 --> 00:11:06.955
It allows us to switch on the big and power-hungry air conditioner

00:11:06.955 --> 00:11:10.914
with a low-voltage signal wire controlled by a thermostat.

00:11:10.914 --> 00:11:15.080
But there are actually more benefits to this
approach than it may seem.

00:11:15.080 --> 00:11:19.178
If you look closely at the thermostat wiring
once it enters the air conditioner,

00:11:19.178 --> 00:11:23.380
you’ll notice that it’s not directly connected to the contactor.

00:11:23.380 --> 00:11:29.040
It actually heads inside to a pressure switch
attached to the refrigerant lines.

00:11:29.040 --> 00:11:31.086
That switch is normally closed,

00:11:31.086 --> 00:11:38.180
but if the refrigerant pressure should get too high it will open
 and break the circuit powering the contactor.

00:11:38.180 --> 00:11:42.801
That will of course shut off the air conditioner,
protecting its compressor from damage.

00:11:42.801 --> 00:11:47.472
More sophisticated systems might have multiple
safety switches all arranged in series

00:11:47.472 --> 00:11:54.992
so that if any one of them opens, the contactor will, too,
and thus power is removed from the compressors or whatever else.

00:11:54.992 --> 00:11:58.655
Without the help of a contactor, every one of those safety devices

00:11:58.655 --> 00:12:06.090
would have to break the full operating current of the motors - 
which is not only difficult for a switch to do,

00:12:06.090 --> 00:12:11.929
but would also require a maze of heavy-gauge
wiring capable of handling the full load of the machine

00:12:11.929 --> 00:12:15.831
to stop by and run through every safety device.

00:12:15.831 --> 00:12:19.384
Anyway, before we get too far lost in HVAC trivia,

00:12:19.384 --> 00:12:23.556
I do want to go back to that current-handling ability of the contactor.

00:12:23.556 --> 00:12:26.237
Remember the locked rotor amps thing?

00:12:26.237 --> 00:12:31.410
Well, I’ve got a fancy multimeter that can
tell us the current spike that the contactor has to deal with.

00:12:31.410 --> 00:12:32.786
[unit switches on]

00:12:32.786 --> 00:12:40.370
That’s not quite as high as the LRA on the data plate, 
but 55.1 amps is still quite a spike!

00:12:40.370 --> 00:12:44.916
Thanks to the fast action of the contacts, though, hardly any arcing occurs.

00:12:45.855 --> 00:12:51.310
Hardly any isn’t “none,” though, and already we can see pitting on the contacts.

00:12:51.310 --> 00:12:57.161
These don’t last forever, and the need to replace a contactor here and there
is certainly not out of the question.

00:12:57.434 --> 00:12:59.800
It could be much worse, though.

00:12:59.800 --> 00:13:04.697
If I use my high-tech insulated poking device, 
I can create some gnarly arcing -

00:13:04.697 --> 00:13:12.839
especially because right now the compressor’s rotor is in fact locked
as it can’t overcome the high pressure in the system right now.

00:13:12.839 --> 00:13:15.672
You can hear it humming but it's not turning.

00:13:16.428 --> 00:13:23.226
[abnormal buzzing and humming when contactor is pushed in]

00:13:23.226 --> 00:13:28.046
This is why modern thermostats might delay
the startup of your air conditioner.

00:13:28.046 --> 00:13:33.639
The compressor needs some time for the refrigerant
pressures to equalize or it may not be able to start.

00:13:33.639 --> 00:13:37.535
And if left powered on in this locked state
for any length of time,

00:13:37.535 --> 00:13:43.540
that can damage the compressor as its motor windings
 will get very hot very quickly.

00:13:43.540 --> 00:13:49.460
The compressor usually has its own overload protection,
so it’s generally not too much of a concern,

00:13:49.460 --> 00:13:54.791
and the circuit breaker protecting this circuit would
probably trip before that even comes into play but

00:13:54.791 --> 00:13:57.135
that’s annoying if nothing else so

00:13:57.135 --> 00:14:04.206
pretty much any electronic thermostat will enforce a delay period
between the last shutdown and the next startup.

00:14:04.728 --> 00:14:07.418
But I said we wouldn’t get lost in HVAC trivia.

00:14:07.418 --> 00:14:13.320
Of course, there are many other things one can do with a contactor
besides just turn on an air conditioner.

00:14:13.320 --> 00:14:18.680
For a start, 24V is by no means the only option for the coil voltage.

00:14:18.680 --> 00:14:22.274
In fact, through the Magic of Buying Two of Them,

00:14:22.274 --> 00:14:25.843
I have a 120V contactor right here.

00:14:25.843 --> 00:14:32.018
This is nearly identical to the first one,
but the coil runs on ordinary AC power.

00:14:32.018 --> 00:14:40.250
This could be useful to, say, turn on some high-voltage overhead lighting in a gymnasium or warehouse with an ordinary light switch.

00:14:40.250 --> 00:14:46.010
Or perhaps create some sort of mystery box
for controlling whether a water heater has power or not.

00:14:46.740 --> 00:14:49.180
I’m still not letting you look inside of there, though.

00:14:49.180 --> 00:14:54.190
There are plenty of contactors that have three poles
rather than just the two you see here,

00:14:54.190 --> 00:14:57.547
and allows them to send power to large three-phase motors,

00:14:57.547 --> 00:15:01.370
like for instance exhaust fans in a commercial kitchen.

00:15:01.370 --> 00:15:08.407
With a 120V control coil, you could wire that contactor
(or multiple contactors) up with the room lights

00:15:08.407 --> 00:15:11.928
to ensure that those fans run whenever the kitchen is occupied.

00:15:11.928 --> 00:15:16.607
And inside really big HVAC systems with three-phase compressors,

00:15:16.607 --> 00:15:20.802
you’ll find them there, too, though usually with 24V coils.

00:15:20.802 --> 00:15:27.860
Really, any time you need to control a big electrical device,
a contactor is probably doing the gruntwork.

00:15:27.860 --> 00:15:33.149
And for really big motors, there’s a subset of contactors
known as motor starters.

00:15:33.149 --> 00:15:37.589
Those might be as simple as a conventional contactor
which can monitor current flow

00:15:37.589 --> 00:15:41.467
and will shut down the motor if it exceeds a certain threshold.

00:15:41.467 --> 00:15:49.365
But it might also involve multiple contactors that can dynamically rewire a motor between two configurations.

00:15:49.365 --> 00:15:54.000
Really gigantic three-phase motors pull so
much current from a stop

00:15:54.000 --> 00:15:59.483
that it’s effectively impossible to start them
by simply applying power as normal.

00:15:59.483 --> 00:16:06.440
So instead, the motor is temporarily run with
its windings wired in a star- or Y-configuration

00:16:06.440 --> 00:16:10.427
which limits its starting current at the expense of reducing torque.

00:16:10.427 --> 00:16:14.866
Once it’s up to a predetermined speed and
it can safely run at its full power,

00:16:14.866 --> 00:16:18.268
the motor’s windings are switched to a delta configuration,

00:16:18.268 --> 00:16:25.534
and that’s all done with some contactors and timers which form 
a star-delta (or Y-delta) motor starter.

00:16:25.534 --> 00:16:27.860
But why stop at just three poles?

00:16:27.860 --> 00:16:32.399
One of my favorite contactors is the answer to a question I’ve long had:

00:16:32.399 --> 00:16:37.430
how do big buildings turn on so many lights at the same time?

00:16:37.430 --> 00:16:44.169
Think of, like, a hotel with a parking lot, 
exterior wall sconces, signage, bollard lights in pathways,

00:16:44.169 --> 00:16:50.950
and somehow all of those lights, even though they’re
all over the building and can’t possibly be on the same circuits,

00:16:50.950 --> 00:16:54.352
are automatically coming on together at dusk.

00:16:54.352 --> 00:16:56.249
How’s that happening?

00:16:56.249 --> 00:16:59.560
Well, with one of these gnarly contactors.

00:16:59.560 --> 00:17:03.377
You can have perhaps a dozen circuits all controlled by this thing,

00:17:03.377 --> 00:17:05.544
they don’t even need to be the same voltage,

00:17:05.544 --> 00:17:09.796
and it can be hooked up to either a mechanical timer or a photocell.

00:17:09.796 --> 00:17:13.982
One of these might even control the lights in a large store or warehouse,

00:17:13.982 --> 00:17:19.864
allowing you to switch on dozens of kilowatts of lighting
with just a single ordinary light switch.

00:17:19.864 --> 00:17:23.674
And that really gets to the heart of what contactors do.

00:17:23.674 --> 00:17:28.969
Like relays, they are electrically-operated
switches that we can do pretty much anything with.

00:17:28.969 --> 00:17:35.278
But they’re just more focused on raw power-handling
ability than they are speed or complexity.

00:17:35.278 --> 00:17:40.913
And while I’ve talked about a few types that are out there,
trust me there are plenty more.

00:17:40.913 --> 00:17:48.400
Take a look at speed control for locomotive
DC traction motors if you want to see some wild contactor configurations.

00:17:48.400 --> 00:17:52.320
The role of the contactor is arguably changing, though.

00:17:52.320 --> 00:17:55.948
While this one is doing a fine job of controlling my air conditioner,

00:17:55.948 --> 00:17:59.730
the on-or-off nature of it is quite limiting.

00:17:59.730 --> 00:18:02.934
The compressor is just a simple AC induction motor,

00:18:02.934 --> 00:18:09.995
and with a contactor the only thing we can feed to it is
raw 240V AC power at 60 Hz,

00:18:09.995 --> 00:18:15.630
so the motor will only ever run at the two speeds of high or off.

00:18:15.630 --> 00:18:22.935
But we are starting to see variable frequency drives proliferate into more and more
air conditioning, heat pump, and refrigeration systems.

00:18:22.935 --> 00:18:28.370
They’ve been common on mini-splits for many years now,
often marketed as an “inverter” compressor.

00:18:28.370 --> 00:18:33.546
And these systems allow us to spin the motors
at virtually any speed we want by, in essence,

00:18:33.546 --> 00:18:38.468
creating our own flavor of AC voltage with fancy electronicals.

00:18:38.468 --> 00:18:41.998
Some might view this as a needless layer of complexity,

00:18:41.998 --> 00:18:46.375
but when we can spin the compressor (and fans) and any arbitrary speed,

00:18:46.375 --> 00:18:52.710
we can optimize the device’s operating efficiency
for any given load which can save a lot of energy.

00:18:53.570 --> 00:18:56.141
Yeah it’s not strictly necessary,

00:18:56.141 --> 00:19:03.400
but the operating characteristics of a refrigeration system change
depending on the temperatures both inside and out.

00:19:03.400 --> 00:19:09.421
In this footage, it was only mildly warm outside
and inside the temperature was actually kinda chilly.

00:19:09.421 --> 00:19:14.767
And with such a small load the air conditioner was only drawing about 7 amps.

00:19:14.767 --> 00:19:21.361
Keep in mind that its rated load, when including the fan,
should be somewhere north of 13 amps.

00:19:21.361 --> 00:19:27.929
The compressor just isn’t working that hard
because the refrigerant pressures it’s fighting against are quite low.

00:19:27.929 --> 00:19:35.541
But because the compressor can only operate at full speed,
it’s always trying to pump the same volume of refrigerant.

00:19:35.541 --> 00:19:40.811
Yes, it’s using less power than it would
if it were really hot out since the pressures are lower,

00:19:40.811 --> 00:19:47.731
but it could be using even less to deliver the same amount of cooling
if it could simply slow itself down.

00:19:47.731 --> 00:19:50.865
That would reduce pumping and frictional losses in the compressor,

00:19:50.865 --> 00:19:56.059
and we could even slow down the condenser fan
because we don’t need as much heat transfer.

00:19:56.059 --> 00:19:57.868
Over the lifetime of the air conditioner,

00:19:57.868 --> 00:20:04.860
there’s a lot of energy being left on the table
if you can’t dynamically adjust for load conditions.

00:20:04.860 --> 00:20:12.390
And that’s why this thing is only rated at 14 SEER
while my cheap mini-split attains 19 SEER.

00:20:12.390 --> 00:20:17.320
Of course, the downside is that the VFD boards
required for variable-speed compressoring

00:20:17.320 --> 00:20:20.680
are a lot more expensive than contactors.

00:20:20.680 --> 00:20:23.548
These things cost about $15 bucks retail,

00:20:23.548 --> 00:20:27.016
and a replacement inverter board is, uh,

00:20:27.016 --> 00:20:28.720
more than that.

00:20:28.720 --> 00:20:35.046
It’s not impossible to design a very robust
inverter board that should last the life of an air conditioner or heat pump,

00:20:35.046 --> 00:20:40.960
and I’m happy to report that my cheap mini split
is still pumping just fine after four winters now.

00:20:40.960 --> 00:20:43.540
But I do get the concern.

00:20:43.540 --> 00:20:51.000
In a similar vein, electromechanical contactors
like these are starting to become displaced by solid-state contactors.

00:20:51.000 --> 00:20:55.497
Rather than rely on an electromagnet and physical
movement of copper links,

00:20:55.497 --> 00:21:02.020
those devices use electronic components like transistors or triacs
to turn the flow of power on and off.

00:21:02.020 --> 00:21:06.854
They are at least in theory more robust than
an electromechanical device,

00:21:06.854 --> 00:21:11.490
but they are a lot more expensive and aren’t suitable
for every application.

00:21:11.490 --> 00:21:15.690
It is effectively the same device,
just with different technology inside of it,

00:21:15.690 --> 00:21:17.630
but it is interesting to note.

00:21:17.630 --> 00:21:24.111
However, just because we might be using contactors less as a means of control

00:21:24.111 --> 00:21:26.520
doesn’t mean we’re giving them up altogether.

00:21:26.520 --> 00:21:32.919
Increasingly, we see them getting used as
isolation devices that are mainly used for safety.

00:21:32.919 --> 00:21:36.515
As I talked about in my video on electric
vehicle supply equipment,

00:21:36.515 --> 00:21:43.940
your standard AC car charger has a contactor inside of it to
control whether the charge cord has voltage on it or not.

00:21:43.940 --> 00:21:48.136
That contactor is really the only active component
in one of these chargers,

00:21:48.136 --> 00:21:53.388
and the incoming power wires get connected
straight through to the charge cable when it’s pulled in.

00:21:54.234 --> 00:21:59.970
But this contactor shouldn’t ever operate
under load except in an emergency.

00:21:59.970 --> 00:22:02.930
It will close before the car starts drawing power,

00:22:02.930 --> 00:22:10.226
and a switch in the charger handle will signal to the car
to immediately stop pulling current when you reach to unplug it,

00:22:10.226 --> 00:22:14.100
so the load will instantly drop off before the contactor opens.

00:22:14.491 --> 00:22:18.857
It’s really only there to kill power to
the cord when it’s not plugged into a car

00:22:19.300 --> 00:22:22.334
(or on the rare occasion it detects a fault).

00:22:22.334 --> 00:22:28.706
And actually, an electric car’s battery pack 
has some very important contactors inside of it.

00:22:28.706 --> 00:22:35.025
When it’s not turned on, we want to be able to isolate
the high-voltage battery from the rest of the car.

00:22:35.025 --> 00:22:37.006
That’s important not only for safety

00:22:37.006 --> 00:22:41.765
but also keeps the high voltage battery from discharging
when the car’s powered off

00:22:41.765 --> 00:22:44.972
(at least assuming the manufacturer has figured that part out)

00:22:44.972 --> 00:22:46.644
*cough*
Rivian

00:22:46.644 --> 00:22:52.046
So, the battery’s power output is run through some big, beefy DC contactors

00:22:52.046 --> 00:22:56.846
that can physically disconnect the battery cells from the pack’s power terminals.

00:22:56.846 --> 00:23:01.157
And those contactors are controlled by the car’s low-voltage system.

00:23:01.157 --> 00:23:07.169
Electric and hybrid cars have a low-voltage system
that’s basically no different from an ordinary car.

00:23:07.169 --> 00:23:12.700
In fact plenty of EVs have a plain ol’ 12 volt lead acid battery in there somewhere,

00:23:12.700 --> 00:23:17.660
and that battery is what closes in the contactors
inside the traction battery

00:23:17.660 --> 00:23:23.890
so it can send out its spicy voltage to all the spicy stuff
and the car can fully power on.

00:23:23.890 --> 00:23:28.775
If you listen closely as I power on my car,
you can hear those contactors clicking to life.

00:23:28.775 --> 00:23:32.320
[ka-chunk, followed by a buzz, some whirrs, etc]

00:23:32.320 --> 00:23:34.921
There are usually even more contactors, though,

00:23:34.921 --> 00:23:39.945
such as the pair that connects the battery pack to the DC pins of the charge port.

00:23:39.945 --> 00:23:45.746
You only want that to happen when the car
knows for sure that it’s plugged into a DC fast charger,

00:23:45.746 --> 00:23:50.383
because having 400 (or even 800V) DC on these exposed pins

00:23:50.383 --> 00:23:54.020
is not a fun way to learn what a DC arc flash is.

00:23:54.020 --> 00:23:57.733
And depending on other components, there may be even more.

00:23:57.733 --> 00:24:04.795
When I plug my car in to charge, there’s a short symphony of clicking that occurs as the car locks the charge handle to the charge port,

00:24:04.795 --> 00:24:07.354
the charger’s contactor clacks to life,

00:24:07.354 --> 00:24:13.047
and the contactors inside the battery pack click
to allow the onboard charger to juice up the pack's cells.

00:24:13.907 --> 00:24:14.407
[snap]

00:24:14.825 --> 00:24:16.522
[clicketyclack Ka-Chunk]

00:24:16.522 --> 00:24:17.809
[whirr]

00:24:17.809 --> 00:24:18.456
[thunk]

00:24:18.456 --> 00:24:19.207
[CLACK]

00:24:20.094 --> 00:24:24.035
And it’s not over until the disembodied lady sings.

00:24:24.035 --> 00:24:25.957
[seemingly from nowhere]
"Charging Started"

00:24:25.957 --> 00:24:28.489
Anyway, I’ve been going on for long enough.

00:24:28.489 --> 00:24:32.805
Who knew I could stretch a video
on contactors past the 20 minute mark?

00:24:33.743 --> 00:24:35.761
Oh, who am I kidding, we all knew this would happen.

00:24:35.761 --> 00:24:39.252
I’m really not cut out for this whole one minute video stuff.

00:24:40.139 --> 00:24:42.336
I am wearing shorts, though.

00:24:42.336 --> 00:24:43.594
Anyway, thanks for watching.

00:24:44.481 --> 00:24:47.046
♫ flowingly smooth jazz ♫

00:24:50.462 --> 00:24:53.772
But what if you want to control something… big?

00:24:53.772 --> 00:24:55.594
Lll *cough* oops

00:24:55.594 --> 00:24:58.925
Or even switch power from one path to another.

00:24:58.925 --> 00:25:02.304
Often incorporating multiple sets of each compact tight…

00:25:03.738 --> 00:25:05.609
[the line was “contact type”]
Type!

00:25:05.609 --> 00:25:07.249
That’s why it’s so bulky.

00:25:08.579 --> 00:25:09.614
Bulky.

00:25:09.614 --> 00:25:11.648
I hope that sounded OK. I’m not recording that again.

00:25:11.648 --> 00:25:13.187
The large gap.

00:25:13.187 --> 00:25:15.321
The large gap ma… huh guboy

00:25:16.573 --> 00:25:18.642
It could be…

00:25:18.642 --> 00:25:21.706
land somewhere and stop flying.

00:25:21.706 --> 00:25:23.239
[there was a bug in the room]

00:25:23.239 --> 00:25:25.141
Good golly willikers gee.

00:25:25.141 --> 00:25:28.403
... it can safely run at its full power...

00:25:29.889 --> 00:25:31.102
Wrong!

00:25:31.102 --> 00:25:32.622
That’s not how the sentence worked.

00:25:33.874 --> 00:25:37.114
So I'm wondering how many people will have gotten the
"part of a complete breakfast" gag at the beginning.

00:25:37.114 --> 00:25:39.805
Is that mostly an American thing? I can very much see that being the case.

00:25:39.805 --> 00:25:44.699
In case you don't know, breakfast cereal commercials usually say that at the end with imagery of a bowl of your Lucky Charms or whatever beside a glass of orange juice,

00:25:44.699 --> 00:25:48.910
maybe some bacon and eggs, basically acknowledging that the cereal really shouldn't be the only thing you eat for breakfast.

00:25:48.910 --> 00:25:49.581
And that's how my brain works!

